SetTimerSV n, value
Purpose | Change the Set Value (S.V,) of the Timer #n to value. This statement to allow the user to modify the S.V. of the PLC internal timers without changing the source program. A TBASIC function can be written easily to make use of a few digital or analog inputs to modify the SV of these internals timers. The new S.V is also stored in the program EEPROM and hence is non-volatile. (See sample program "set_TCSV.PC4") n should be between 1 and 128. |
Examples | SetTimerSV 10,1234 SetTimerSV 3, GetTimerSV(3)+10 |
Comments: | Timer #10 will assume a S.V. of 1234.. Related : The present values (P.V.) of timers can be read or written directly as integer variables "TimerPV[n]". But the Set Values can only be changed by this function. |
See Also | GetCtrSV( ), GetTimerSV( ) , SetCtrSV |