Purpose |
To set channel #channel of the F-series PLC's Light Dimmer
Control outputs to fire a trigger pulse to opto-isolated TRIAC (or Solid State Relay). The
trigger pulse is fired after a time delay specified by the value parameter (each
unit is equal to about 53 microseconds) and it is measured with respect to the zero
crossing that occur at every half cycle of AC voltage.
channel = |
1 to 12 (which maps to FPLC outputs #5 to 16) |
value
= |
For 50Hz AC signal, range =1 to 188
For 60Hz AC signal, range = 1 to 156 |
Note: when value = 1 the output is fully ON. When value is near is
maximum value the output is fully OFF. Do not set value to larger than the maximum for
each particular AC frequency. |